UPS Topology |
On-Line (Double Conversion) |
Energy Saving |
>96%(ECO), >90%(AC), >89%(Batt) |
Network Interface |
SNAP Card |
Input |
Voltage |
100/110/115/120V |
Voltage Range |
80-150 VAC ± 5%@ 100% load, 55-150 VAC ± 5%@ 50% load, Derate capacity to 80% when the output voltage is adjusted to 100VAC |
Frequency Range |
40 Hz ~ 70 Hz |
Cold Start |
Yes |
Plug Type |
NEMA 5-20P |
Power Factor |
≧ 0.99 @ nominal voltage (100% load) |
Cord Length |
6 ft. |
Output |
Volt Amp Capacity (VA) |
2000 |
Output Watt Capacity (Watts) |
1930 |
Rated Power Factor |
0.96 |
On Battery Waveform |
Sine Wave |
On Battery Frequency |
50/60Hz +/- 3 Hz |
Outlets |
8 |
Outlet Types - Battery & Surge Protected |
8 x NEMA 5-20R |
Crest Factor |
3:1 |
Harmonic Distortion |
≧ 2 % THDv(Linear Load), ≧ 4 % THDv (Non-linear Load) |
Voltage Regulation |
± 1%(Batt) |
Transfer Time (AC to Battery) |
0ms |
Transfer Time (Inverter to Bypass) |
4ms(ECO) |
Battery |
Runtime at Half Load (min) |
10.0 |
Runtime at Full Load (min) |
2.95 |
Battery Type |
Sealed Lead-Acid |
Battery Pack Voltage |
48V |
Battery Quantity |
4 |
Hot-Swappable |
Yes |
Typical Recharge Time |
3 hours recover to 95% capacity @2A charging current., Max charger current 8A |
Extended Battery Module |
GBP48V18AH |
Environment |
Operation Temperature |
0 ? 40 °C(32 ? 104 °F) |
Storage Temperature |
-20 ? 50 °C(-4 ? 122 °F) |
Humidity |
20-90% RH / 10% to 95% (no condensing) |
Certification |
UL FCC |
Unit Dimensions |
Height |
3.5 in. (8.9 cm) |
Length |
20 in. (50.8 cm) |
Width |
17.3 in. (44 cm) |
Master Carton |
Height |
9.75 in. (24.8 cm) |
Length |
27.75 in. (70.5 cm) |
Width |
22 in. (55.9 cm) |
Master Carton Qty. |
1 |
Weight |
Master Carton Wt. |
56.1 lb. (25.5kg) |
Unit Wt. |
46.5 lb. (21.1 kg) |