UPS Topology |
On-Line (Double Conversion) |
Energy Saving |
>96%(ECO), >91%(AC), >90%(Batt) |
Network Interface |
SNMP Card |
Input |
Voltage |
100/110/115/120V |
Voltage Range |
80-150 VAC ± 5%@ 100% load, 55-150 VAC ± 5%@ 50% load, Derate capacity to 80% when the output voltage is adjusted to 100VAC |
Frequency Range |
40 Hz ~ 70 Hz |
Cold Start |
Yes |
Plug Type |
NEMA L5-130 |
Power Factor |
≧ 0.99 @ nominal voltage (100% load) |
Cord Length |
6 ft. |
Output |
Volt Amp Capacity (VA) |
3000 |
Output Watt Capacity (Watts) |
2850 |
Rated Power Factor |
0.96 |
On Battery Waveform |
Sine Wave |
On Battery Frequency |
50/60Hz +/- 3 Hz |
Outlets |
7 |
Outlet Types - Battery & Surge Protected |
7 x NEMA5-20R + 1x NEMA L5-30R |
Crest Factor |
3:1 |
Harmonic Distortion |
≦ 2 % THDv(Linear Load), ≦ 4 % THDv (Non-linear Load) |
Voltage Regulation |
± 1%(Batt) |
Transfer Time (AC to Battery) |
0ms |
Transfer Time (Inverter to Bypass) |
4ms(ECO) |
Battery |
Runtime at Half Load (min) |
2.96 |
Runtime at Full Load (min) |
10.1 |
Battery Type |
Sealed Lead-Acid |
Battery Pack Voltage |
72V |
Battery Quantity |
6 |
Hot-Swappable |
Yes |
Typical Recharge Time |
3 hours recover to 95% capacity @2A charging current., Max charger current 8A |
Extended Battery Module |
GBP72V18AH |
Environment |
Operation Temperature |
0 ? 40 °C(32 ? 104 °F) |
Storage Temperature |
-20 ? 50 °C(-4 ? 122 °F) |
Humidity |
20-90% RH / 10% to 95% (no condensing) |
Certification |
UL FCC |
Unit Dimensions |
Height |
3.5 in. (8.9 cm) |
Length |
24.75 in. (62.8 cm) |
Width |
17.3 in. (44 cm) |
Master Carton |
Height |
9.75 in. (24.8 cm) |
Length |
29.5 in. (74.9 cm) |
Width |
23.5 in. (59.7 cm) |
Master Carton Qty. |
1 |
Weight |
Master Carton Wt. |
76.3 lb. |
Unit Wt. |
65 lb. (29.5 kg) |